| Photo |
Наименование |
Article |
Цена |
|
|
OGNEZA PM(V)-T Fire prevention ventilation sleeve, d 190 (price on request) [Code number: 1r0027]
Details
|
1r0027 |
7 330 rub |
Application purpose:
- For installation with plastic ventilation ducts
- For residential buildings (including apartment buildings), hospitals, hostels, hotels, shopping centers, airports and train stations, industrial enterprises
Characteristics:
- fire resistance not less than EI 180;
- suitable for walls with an additional partition and an air gap between them.

Compound:
- perforated fixed sleeve body;
- metal case of the movable sleeve (painted with polymer powder paint);
- thermally expanding material "OGNEZA-TRM";
- movable sleeve seal;
- lamellas;
- fastening eyelets.
Installation Recommendations:
- installation is carried out at temperatures from -50 °С to +60 °С;
- the installation site is pre-cleaned;
- the attachment points should not have cracks, and the thickness of the hard layer should allow the installation of a fixing metal dowel;
- the gap between the sleeve and the channel wall must be less than 5 mm;
- fixing eyes are bent in the plane of the base of the coupling;
- the coupling is installed in the channel, after which the points of attachment of the lugs to the enclosing structure are marked with a marker.
Diameter: DN 190.
|
|
|
OGNEZA PM(V)-T Fire prevention ventilation sleeve, d 200 (price on request) [Code number: 1r0028]
Details
|
1r0028 |
7 636 rub |
Application purpose:
- For installation with plastic ventilation ducts
- For residential buildings (including apartment buildings), hospitals, hostels, hotels, shopping centers, airports and train stations, industrial enterprises
Characteristics:
- fire resistance not less than EI 180;
- suitable for walls with an additional partition and an air gap between them.

Compound:
- perforated fixed sleeve body;
- metal case of the movable sleeve (painted with polymer powder paint);
- thermally expanding material "OGNEZA-TRM";
- movable sleeve seal;
- lamellas;
- fastening eyelets.
Installation Recommendations:
- installation is carried out at temperatures from -50 °С to +60 °С;
- the installation site is pre-cleaned;
- the attachment points should not have cracks, and the thickness of the hard layer should allow the installation of a fixing metal dowel;
- the gap between the sleeve and the channel wall must be less than 5 mm;
- fixing eyes are bent in the plane of the base of the coupling;
- the coupling is installed in the channel, after which the points of attachment of the lugs to the enclosing structure are marked with a marker.
Diameter: DN 200.
|
|
|
OGNEZA PM(V)-T Fire prevention ventilation sleeve, d 210 (price on request) [Code number: 1r0029]
Details
|
1r0029 |
7 942 rub |
Application purpose:
- For installation with plastic ventilation ducts
- For residential buildings (including apartment buildings), hospitals, hostels, hotels, shopping centers, airports and train stations, industrial enterprises
Characteristics:
- fire resistance not less than EI 180;
- suitable for walls with an additional partition and an air gap between them.

Compound:
- perforated fixed sleeve body;
- metal case of the movable sleeve (painted with polymer powder paint);
- thermally expanding material "OGNEZA-TRM";
- movable sleeve seal;
- lamellas;
- fastening eyelets.
Installation Recommendations:
- installation is carried out at temperatures from -50 °С to +60 °С;
- the installation site is pre-cleaned;
- the attachment points should not have cracks, and the thickness of the hard layer should allow the installation of a fixing metal dowel;
- the gap between the sleeve and the channel wall must be less than 5 mm;
- fixing eyes are bent in the plane of the base of the coupling;
- the coupling is installed in the channel, after which the points of attachment of the lugs to the enclosing structure are marked with a marker.
Diameter: DN 210.
|
|
|
OGNEZA PM(V)-T Fire prevention ventilation sleeve, d 220 (price on request) [Code number: 1r0030]
Details
|
1r0030 |
8 248 rub |
Application purpose:
- For installation with plastic ventilation ducts
- For residential buildings (including apartment buildings), hospitals, hostels, hotels, shopping centers, airports and train stations, industrial enterprises
Characteristics:
- fire resistance not less than EI 180;
- suitable for walls with an additional partition and an air gap between them.

Compound:
- perforated fixed sleeve body;
- metal case of the movable sleeve (painted with polymer powder paint);
- thermally expanding material "OGNEZA-TRM";
- movable sleeve seal;
- lamellas;
- fastening eyelets.
Installation Recommendations:
- installation is carried out at temperatures from -50 °С to +60 °С;
- the installation site is pre-cleaned;
- the attachment points should not have cracks, and the thickness of the hard layer should allow the installation of a fixing metal dowel;
- the gap between the sleeve and the channel wall must be less than 5 mm;
- fixing eyes are bent in the plane of the base of the coupling;
- the coupling is installed in the channel, after which the points of attachment of the lugs to the enclosing structure are marked with a marker.
Diameter: DN 220.
|
|
|
OGNEZA PM(V)-T Fire prevention ventilation sleeve, d 230 (price on request) [Code number: 1r0031]
Details
|
1r0031 |
8 552 rub |
Application purpose:
- For installation with plastic ventilation ducts
- For residential buildings (including apartment buildings), hospitals, hostels, hotels, shopping centers, airports and train stations, industrial enterprises
Characteristics:
- fire resistance not less than EI 180;
- suitable for walls with an additional partition and an air gap between them.

Compound:
- perforated fixed sleeve body;
- metal case of the movable sleeve (painted with polymer powder paint);
- thermally expanding material "OGNEZA-TRM";
- movable sleeve seal;
- lamellas;
- fastening eyelets.
Installation Recommendations:
- installation is carried out at temperatures from -50 °С to +60 °С;
- the installation site is pre-cleaned;
- the attachment points should not have cracks, and the thickness of the hard layer should allow the installation of a fixing metal dowel;
- the gap between the sleeve and the channel wall must be less than 5 mm;
- fixing eyes are bent in the plane of the base of the coupling;
- the coupling is installed in the channel, after which the points of attachment of the lugs to the enclosing structure are marked with a marker.
Diameter: DN 230.
|
|
|
OGNEZA PM(V)-T Fire prevention ventilation sleeve, d 240 (price on request) [Code number: 1r0032]
Details
|
1r0032 |
9 164 rub |
Application purpose:
- For installation with plastic ventilation ducts
- For residential buildings (including apartment buildings), hospitals, hostels, hotels, shopping centers, airports and train stations, industrial enterprises
Characteristics:
- fire resistance not less than EI 180;
- suitable for walls with an additional partition and an air gap between them.

Compound:
- perforated fixed sleeve body;
- metal case of the movable sleeve (painted with polymer powder paint);
- thermally expanding material "OGNEZA-TRM";
- movable sleeve seal;
- lamellas;
- fastening eyelets.
Installation Recommendations:
- installation is carried out at temperatures from -50 °С to +60 °С;
- the installation site is pre-cleaned;
- the attachment points should not have cracks, and the thickness of the hard layer should allow the installation of a fixing metal dowel;
- the gap between the sleeve and the channel wall must be less than 5 mm;
- fixing eyes are bent in the plane of the base of the coupling;
- the coupling is installed in the channel, after which the points of attachment of the lugs to the enclosing structure are marked with a marker.
Diameter: DN 240.
|
|
|
OGNEZA PM (TK) Fire-prevention drain coupling, d 200/160 (price on request) [Code number: 1r0033]
Details
|
1r0033 |
60 720 rub |
Application purpose:
- For fire protection of installation places of roof funnels and drains
- For all types of roof outlets and drains
- For hotels, hostels, entertainment complexes, swimming pools, etc
Fire resistance limit: 180 minutes for roof outlets and 90 minutes for drains.
Operating principle:
During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.
| Size |
Outside diameter |
Through diameter |
Sleeve diameter |
Body fit diameter |
Height |
Minimum overlap thickness |
| |
mm |
mm |
mm |
mm |
mm |
mm |
| 200/160 |
245 |
130 |
200 |
160 |
170 |
200 |
|
|
|
OGNEZA PM (TK) Fire-prevention drain coupling, d 110/110 (price on request) [Code number: 1r0034]
Details
|
1r0034 |
27 600 rub |
Application purpose:
- For fire protection of installation places of roof funnels and drains
- For all types of roof outlets and drains
- For hotels, hostels, entertainment complexes, swimming pools, etc
Fire resistance limit: 180 minutes for roof outlets and 90 minutes for drains.
Operating principle:
During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.
| Size |
Outside diameter |
Through diameter |
Sleeve diameter |
Body fit diameter |
Height |
Minimum overlap thickness |
| |
mm |
mm |
mm |
mm |
mm |
mm |
| 110/110 |
160 |
90 |
110 |
110 |
130 |
100 |
|
|
|
OGNEZA PM (TK) Fire-prevention drain coupling, d 160/110 (price on request) [Code number: 1r0035]
Details
|
1r0035 |
37 260 rub |
Application purpose:
- For fire protection of installation places of roof funnels and drains
- For all types of roof outlets and drains
- For hotels, hostels, entertainment complexes, swimming pools, etc
Fire resistance limit: 180 minutes for roof outlets and 90 minutes for drains.
Operating principle:
During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.
| Size |
Outside diameter |
Through diameter |
Sleeve diameter |
Body fit diameter |
Height |
Minimum overlap thickness |
| |
mm |
mm |
mm |
mm |
mm |
mm |
| 160/110 |
200 |
90 |
160 |
110 |
160 |
130 |
|
|
|
OGNEZA PM (TK) Fire-prevention drain coupling, d 160/160 (price on request) [Code number: 1r0036]
Details
|
1r0036 |
58 512 rub |
Application purpose:
- For fire protection of installation places of roof funnels and drains
- For all types of roof outlets and drains
- For hotels, hostels, entertainment complexes, swimming pools, etc
Fire resistance limit: 180 minutes for roof outlets and 90 minutes for drains.
Operating principle:
During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.
| Size |
Outside diameter |
Through diameter |
Sleeve diameter |
Body fit diameter |
Height |
Minimum overlap thickness |
| |
mm |
mm |
mm |
mm |
mm |
mm |
| 160/160 |
200 |
130 |
160 |
160 |
160 |
130 |
|
|
|
OGNEZA PM Fire prevention sleeve, lock type "Light", gray, d 160 [Code number: 1r0058]
Details
|
1r0058 |
1 896 rub |
Application purpose:
- For pipeline communications made of combustible plastic materials (PP, PE, PVC)
- For residential (including multi-apartment) buildings, hotels and hostels, social and medical institutions, shopping centers, airports and railway stations, industrial enterprises, etc
- To protect premises from fire and smoke
Characteristics:
- The case is detachable, there is a tie-lock, so that the fire coupling can be used on already installed pipelines;
- Metal parts are powder coated for corrosion protection;
- Swelling ratio: not less than 900%;
- Product color: gray;
- Lock type: Light;
- Fire resistance limit: 180 minutes;
- Service life: 30 years.
Operating principle:
During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.
Installation method

PM structure
- The case is a metal cuff and is made of cold-rolled or galvanized steel (thickness from 0.5 to 2 mm). Painted with weatherproof paint.
- The case is connected using a reliable Russian-made latch made of galvanized steel.
- The fire-retardant liner is located inside the coupling, held by the cloves bent inward. They also provide directional expansion of the fire retardant liner during a fire.
- The eyelets with holes can be easily bent. Their length is 35 mm, which simplifies installation.
| Size |
Inner diameter |
Height |
Outside diameter |
Insert thickness |
Weight |
| |
mm |
mm |
mm |
mm |
kg |
| PM-160 |
160 |
90 |
195 |
15 |
0,900 |
Download installation instruction: OGNEZA Fire collar
|
|
|
OGNEZA-PM-K Cable penetration, gray, d 110 (price on request) [Code number: 1r0112]
Details
|
1r0112 |
|
Application purpose:
- To block the spread of fire along cable lines
- For installation in places of passage of cables, pipelines of engineering systems, technological pipelines
Characteristics:
- due to the fact that the coupling body is detachable, it can be mounted on an already laid cable line;
- metal parts are powder coated to reduce corrosion (colour: grey);
- triggers approximately 15 seconds after the temperature rises to +150°C;
- expansion coefficient: not less than 900%;
- the fire resistance limit is 180 minutes;
- service life: 30 years (at temperatures from -50 to +80°C).
Installation recommendations:
- the thickness of the walls where the cable passage is mounted must be at least 150 mm;
- the cable sleeve is installed on both sides in a metal sleeve in the ceiling along the cable lines. If there is no sleeve, installation is possible in a hole sealed with mineral wool;
- fastened with anchor bolts or metal dowels.
| Size |
Diameter |
Coupling height |
Insert width |
Number of inserts |
Weight |
| |
mm |
mm |
mm |
mm |
gr |
| PM-K-110 |
110 |
32 |
30 |
4 |
80/100 |
|
|
|
OGNEZA-PM-K Cable penetration, gray, d 125 (price on request) [Code number: 1r0113]
Details
|
1r0113 |
|
Application purpose:
- To block the spread of fire along cable lines
- For installation in places of passage of cables, pipelines of engineering systems, technological pipelines
Characteristics:
- due to the fact that the coupling body is detachable, it can be mounted on an already laid cable line;
- metal parts are powder coated to reduce corrosion (colour: grey);
- triggers approximately 15 seconds after the temperature rises to +150°C;
- expansion coefficient: not less than 900%;
- the fire resistance limit is 180 minutes;
- service life: 30 years (at temperatures from -50 to +80°C).
Installation recommendations:
- the thickness of the walls where the cable passage is mounted must be at least 150 mm;
- the cable sleeve is installed on both sides in a metal sleeve in the ceiling along the cable lines. If there is no sleeve, installation is possible in a hole sealed with mineral wool;
- fastened with anchor bolts or metal dowels.
| Size |
Diameter |
Coupling height |
Insert width |
Number of inserts |
Weight |
| |
mm |
mm |
mm |
mm |
gr |
| PM-K-125 |
125 |
32 |
30 |
7 |
200 |
|
|
|
OGNEZA-PM-K Cable penetration, gray, d 40/20 (price on request) [Code number: 1r0114]
Details
|
1r0114 |
|
Application purpose:
- To block the spread of fire along cable lines
- For installation in places of passage of cables, pipelines of engineering systems, technological pipelines
Characteristics:
- due to the fact that the coupling body is detachable, it can be mounted on an already laid cable line;
- metal parts are powder coated to reduce corrosion (colour: grey);
- triggers approximately 15 seconds after the temperature rises to +150°C;
- expansion coefficient: not less than 900%;
- the fire resistance limit is 180 minutes;
- service life: 30 years (at temperatures from -50 to +80°C).
Installation recommendations:
- the thickness of the walls where the cable passage is mounted must be at least 150 mm;
- the cable sleeve is installed on both sides in a metal sleeve in the ceiling along the cable lines. If there is no sleeve, installation is possible in a hole sealed with mineral wool;
- fastened with anchor bolts or metal dowels.
| Size |
Diameter |
Coupling height |
Insert width |
Number of inserts |
Weight |
| |
mm |
mm |
mm |
mm |
gr |
| PM-K-20/40 |
20-40 |
32 |
30 |
2/- |
55 |
|
|
|
OGNEZA-PM-K Cable penetration, gray, d 50 (price on request) [Code number: 1r0115]
Details
|
1r0115 |
|
Application purpose:
- To block the spread of fire along cable lines
- For installation in places of passage of cables, pipelines of engineering systems, technological pipelines
Characteristics:
- due to the fact that the coupling body is detachable, it can be mounted on an already laid cable line;
- metal parts are powder coated to reduce corrosion (colour: grey);
- triggers approximately 15 seconds after the temperature rises to +150°C;
- expansion coefficient: not less than 900%;
- the fire resistance limit is 180 minutes;
- service life: 30 years (at temperatures from -50 to +80°C).
Installation recommendations:
- the thickness of the walls where the cable passage is mounted must be at least 150 mm;
- the cable sleeve is installed on both sides in a metal sleeve in the ceiling along the cable lines. If there is no sleeve, installation is possible in a hole sealed with mineral wool;
- fastened with anchor bolts or metal dowels.
| Size |
Diameter |
Coupling height |
Insert width |
Number of inserts |
Weight |
| |
mm |
mm |
mm |
mm |
gr |
| PM-K-50 |
50 |
32 |
30 |
2/2 |
55 |
|
|
|
OGNEZA-PM-K Cable penetration, gray, d 65 (price on request) [Code number: 1r0116]
Details
|
1r0116 |
|
Application purpose:
- To block the spread of fire along cable lines
- For installation in places of passage of cables, pipelines of engineering systems, technological pipelines
Characteristics:
- due to the fact that the coupling body is detachable, it can be mounted on an already laid cable line;
- metal parts are powder coated to reduce corrosion (colour: grey);
- triggers approximately 15 seconds after the temperature rises to +150°C;
- expansion coefficient: not less than 900%;
- the fire resistance limit is 180 minutes;
- service life: 30 years (at temperatures from -50 to +80°C).
Installation recommendations:
- the thickness of the walls where the cable passage is mounted must be at least 150 mm;
- the cable sleeve is installed on both sides in a metal sleeve in the ceiling along the cable lines. If there is no sleeve, installation is possible in a hole sealed with mineral wool;
- fastened with anchor bolts or metal dowels.
| Size |
Diameter |
Coupling height |
Insert width |
Number of inserts |
Weight |
| |
mm |
mm |
mm |
mm |
gr |
| PM-K-65 |
65 |
32 |
30 |
4 |
55 |
|
|
|
OGNEZA-PM-K Cable penetration, gray, d 80 (price on request) [Code number: 1r0117]
Details
|
1r0117 |
|
Application purpose:
- To block the spread of fire along cable lines
- For installation in places of passage of cables, pipelines of engineering systems, technological pipelines
Characteristics:
- due to the fact that the coupling body is detachable, it can be mounted on an already laid cable line;
- metal parts are powder coated to reduce corrosion (colour: grey);
- triggers approximately 15 seconds after the temperature rises to +150°C;
- expansion coefficient: not less than 900%;
- the fire resistance limit is 180 minutes;
- service life: 30 years (at temperatures from -50 to +80°C).
Installation recommendations:
- the thickness of the walls where the cable passage is mounted must be at least 150 mm;
- the cable sleeve is installed on both sides in a metal sleeve in the ceiling along the cable lines. If there is no sleeve, installation is possible in a hole sealed with mineral wool;
- fastened with anchor bolts or metal dowels.
| Size |
Diameter |
Coupling height |
Insert width |
Number of inserts |
Weight |
| |
mm |
mm |
mm |
mm |
gr |
| PM-K-80 |
80 |
32 |
30 |
4 |
65 |
|
|
|
OGNEZA-PM-K Cable penetration, gray, d 90 (price on request) [Code number: 1r0118]
Details
|
1r0118 |
|
Application purpose:
- To block the spread of fire along cable lines
- For installation in places of passage of cables, pipelines of engineering systems, technological pipelines
Characteristics:
- due to the fact that the coupling body is detachable, it can be mounted on an already laid cable line;
- metal parts are powder coated to reduce corrosion (colour: grey);
- triggers approximately 15 seconds after the temperature rises to +150°C;
- expansion coefficient: not less than 900%;
- the fire resistance limit is 180 minutes;
- service life: 30 years (at temperatures from -50 to +80°C).
Installation recommendations:
- the thickness of the walls where the cable passage is mounted must be at least 150 mm;
- the cable sleeve is installed on both sides in a metal sleeve in the ceiling along the cable lines. If there is no sleeve, installation is possible in a hole sealed with mineral wool;
- fastened with anchor bolts or metal dowels.
| Size |
Diameter |
Coupling height |
Insert width |
Number of inserts |
Weight |
| |
mm |
mm |
mm |
mm |
gr |
| PM-K-90 |
90 |
32 |
30 |
4 |
75 |
|
|
|
OGNEZA Fire collar, lock type "Light", gray, d 65 [Code number: 1r0148]
Details
|
1r0148 |
438 rub |
|
|
|
|
OGNEZA Fireproof sound insulation sleeve, d 110/100 (price on request) [Code number: pgz_110_100]
Details
|
pgz_110_100 |
3 450 rub |
Attention! New requirements of JV 30.13330.2016 for the protection of plastic pipes are mandatory from the summer of 2019.
The passage of plastic pipes through ceilings in residential and office buildings should include:
- soundproofing;
- fire protection;
- sealing.
OGNEZA-PGZ is a complex product for fire protection of plastic pipes. It consists of a split metal body, a thermally expanding material, a soundproofing layer of mineral wool and a fireproof sealant for waterproofing.

Characteristics:
- There are no analogues
- Easy installation in 3 movements
- It is possible to manufacture for any thickness of coatings
- All standard sizes
- Fire resistance EI 180
- Reduces noise by at least 30 dB
| Size |
Slab Thickness |
Inner diameter |
Outside Diameter |
Height for finishing / monolith |
Through hole diameter (not less than) |
| |
mm |
mm |
mm |
mm |
mm |
| 110/100 |
100 |
114 |
176 |
155/185 |
182 |
Installation instructions

Download product installation manual: OGNEZA Fireproof sound insulation sleeve
|