Logo
Ru| En
Loading

OGNEZA-PM fire collars

"OGNEZA-PM" fire collars are designed to protect the premises from fire and smoke during fires.

The fire collar consists of a metal case and a polymer liner.

  • The housing of the fire collar is made of cold-rolled or galvanized steel with a thickness of 0.5 to 2 mm. Steel is painted with weather resistant paint.
  • The lock is made of galvanized steel and is coated with paint in the color of the collar.
  • There are inward-curved teeth which hold the fire-retardant liner inside the housing as well as provide its directional expansion.
  • Fastening lugs easy to bend. The length of mounting lugs is 35 mm, there are models with elongated lugs (70 mm) for pipes which are mounted in metal sleeves that are used in monolithic construction.
  • The main working component of the fire collar is a flame retardant heat-expanding tape liner. It is made of thermally expanding material OGNEZA-TPM developed by the Ogneza company and based on rubber and graphite. The liner is plastic, odorless, neutral to water, non-toxic. It keeps properties for 30 years.
Photo Name Article Price
OGNEZA Fire collar, lock type "Light", red, d 80 [Code number: 1r0147]
Details
1r0147 474 rub
OGNEZA Fire collar, lock type "Light", gray, d 65 [Code number: 1r0148]
Details
1r0148 420 rub
OGNEZA Fire collar, lock type "Light", red, d 65 [Code number: 1r0149]
Details
1r0149 420 rub
OGNEZA Fireproof sound insulation sleeve, d 110/100 (price on request) [Code number: pgz_110_100]
Details
pgz_110_100

Attention! New requirements of JV 30.13330.2016 for the protection of plastic pipes are mandatory from the summer of 2019.

The passage of plastic pipes through ceilings in residential and office buildings should include:

  • soundproofing;
  • fire protection;
  • sealing.

OGNEZA-PGZ is a complex product for fire protection of plastic pipes. It consists of a split metal body, a thermally expanding material, a soundproofing layer of mineral wool and a fireproof sealant for waterproofing.

Characteristics:

  • There are no analogues
  • Easy installation in 3 movements
  • It is possible to manufacture for any thickness of coatings
  • All standard sizes
  • Fire resistance EI 180
  • Reduces noise by at least 30 dB
Size Slab Thickness Inner diameter Outside Diameter Height for finishing / monolith Through hole diameter (not less than)
  mm mm mm mm mm
110/100 100 114 176 155/185 182

Installation instructions

Download product installation manual: OGNEZA Fireproof sound insulation sleeve OGNEZA Fireproof sound insulation sleeve

OGNEZA Fireproof sound insulation sleeve, d 110/200 (price on request) [Code number: pgz_110_200]
Details
pgz_110_200

Application purpose:

  • For pipeline communications made of combustible plastic materials (PP, PE, PVC)
  • For residential and administrative buildings, hotels and shopping centers, apartment buildings, social and medical institutions, as well as railway stations
  • To protect premises from fire and smoke

Characteristics:

  • It is a complex product, which consists of a metal detachable body, a special material that expands with increasing temperature, a layer of soundproof mineral wool, and a fire sealant;
  • Allows you to reduce the cost of installing equipment for fire protection and sound insulation;
  • Swelling ratio: not less than 900%;
  • Product color: red;
  • Fire resistance limit: 180 minutes;
  • Operation inertia: no more than 4 minutes.

According to the current regulations, the passages of plastic pipes through the ceilings must be protected from fire, while they must comply with the requirements for sound insulation. And fire-fighting muds of Ogneza PGZ meet the established requirements.

Operating principle:

During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.

Size Slab Thickness Inner diameter Outside Diameter Height for finishing / monolith Through hole diameter (not less than)
  mm mm mm mm mm
110/200 200 114 176 255/285 182

Download product installation manual: OGNEZA Fireproof sound insulation sleeve OGNEZA Fireproof sound insulation sleeve

OGNEZA Fireproof sound insulation sleeve, d 110/250 (price on request) [Code number: pgz_110_250]
Details
pgz_110_250

Application purpose:

  • For pipeline communications made of combustible plastic materials (PP, PE, PVC)
  • For residential and administrative buildings, hotels and shopping centers, apartment buildings, social and medical institutions, as well as railway stations
  • To protect premises from fire and smoke

Characteristics:

  • It is a complex product, which consists of a metal detachable body, a special material that expands with increasing temperature, a layer of soundproof mineral wool, and a fire sealant;
  • Allows you to reduce the cost of installing equipment for fire protection and sound insulation;
  • Swelling ratio: not less than 900%;
  • Product color: red;
  • Fire resistance limit: 180 minutes;
  • Operation inertia: no more than 4 minutes.

According to the current regulations, the passages of plastic pipes through the ceilings must be protected from fire, while they must comply with the requirements for sound insulation. And fire-fighting muds of Ogneza PGZ meet the established requirements.

Operating principle:

During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.

Size Slab Thickness Inner diameter Outside Diameter Height for finishing / monolith Through hole diameter (not less than)
  mm mm mm mm mm
110/250 250 114 176 305/335 182

Download product installation manual: OGNEZA Fireproof sound insulation sleeve OGNEZA Fireproof sound insulation sleeve

OGNEZA Fireproof sound insulation sleeve, d 110/300 (price on request) [Code number: pgz_110_300]
Details
pgz_110_300

Application purpose:

  • For pipeline communications made of combustible plastic materials (PP, PE, PVC)
  • For residential and administrative buildings, hotels and shopping centers, apartment buildings, social and medical institutions, as well as railway stations
  • To protect premises from fire and smoke

Characteristics:

  • It is a complex product, which consists of a metal detachable body, a special material that expands with increasing temperature, a layer of soundproof mineral wool, and a fire sealant;
  • Allows you to reduce the cost of installing equipment for fire protection and sound insulation;
  • Swelling ratio: not less than 900%;
  • Product color: red;
  • Fire resistance limit: 180 minutes;
  • Operation inertia: no more than 4 minutes.

According to the current regulations, the passages of plastic pipes through the ceilings must be protected from fire, while they must comply with the requirements for sound insulation. And fire-fighting muds of Ogneza PGZ meet the established requirements.

Operating principle:

During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.

Size Slab Thickness Inner diameter Outside Diameter Height for finishing / monolith Through hole diameter (not less than)
  mm mm mm mm mm
110/300 300 114 176 355/385 182

Download product installation manual: OGNEZA Fireproof sound insulation sleeve OGNEZA Fireproof sound insulation sleeve

OGNEZA Fireproof sound insulation sleeve, d 50/100 (price on request) [Code number: pgz_50_100]
Details
pgz_50_100

Attention! New requirements of JV 30.13330.2016 for the protection of plastic pipes are mandatory from the summer of 2019.

The passage of plastic pipes through ceilings in residential and office buildings should include:

  • soundproofing;
  • fire protection;
  • sealing.

OGNEZA-PGZ is a complex product for fire protection of plastic pipes. It consists of a split metal body, a thermally expanding material, a soundproofing layer of mineral wool and a fireproof sealant for waterproofing.

Characteristics:

  • There are no analogues
  • Easy installation in 3 movements
  • It is possible to manufacture for any thickness of coatings
  • All standard sizes
  • Fire resistance EI 180
  • Reduces noise by at least 30 dB
Size Slab Thickness Inner diameter Outside Diameter Height for finishing / monolith Through hole diameter (not less than)
  mm mm mm mm mm
50/100 100 54 116 155/185 122

Installation instructions

Download product installation manual: OGNEZA Fireproof sound insulation sleeve OGNEZA Fireproof sound insulation sleeve

OGNEZA Fireproof sound insulation sleeve, d 50/250 (price on request) [Code number: pgz_50_250]
Details
pgz_50_250

Application purpose:

  • For pipeline communications made of combustible plastic materials (PP, PE, PVC)
  • For residential and administrative buildings, hotels and shopping centers, apartment buildings, social and medical institutions, as well as railway stations
  • To protect premises from fire and smoke

Characteristics:

  • It is a complex product, which consists of a metal detachable body, a special material that expands with increasing temperature, a layer of soundproof mineral wool, and a fire sealant;
  • Allows you to reduce the cost of installing equipment for fire protection and sound insulation;
  • Swelling ratio: not less than 900%;
  • Product color: red;
  • Fire resistance limit: 180 minutes;
  • Operation inertia: no more than 4 minutes.

According to the current regulations, the passages of plastic pipes through the ceilings must be protected from fire, while they must comply with the requirements for sound insulation. And fire-fighting muds of Ogneza PGZ meet the established requirements.

Operating principle:

During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.

Size Slab Thickness Inner diameter Outside Diameter Height for finishing / monolith Through hole diameter (not less than)
  mm mm mm mm mm
50/250 250 54 116 305/335 122

Download product installation manual: OGNEZA Fireproof sound insulation sleeve OGNEZA Fireproof sound insulation sleeve

OGNEZA PGZ-M Fireproof sound insulation sleeve, d 110/200 (price on request) [Code number: pgz_m_110_200]
Details
pgz_m_110_200
OGNEZA PGZ-M Fireproof sound insulation sleeve, d 110/250 (price on request) [Code number: pgz_m_110_250]
Details
pgz_m_110_250
OGNEZA Fire collar, lock type "Light", d 110/108 (price on request) [Code number: pm_110_108_light]
Details
pm_110_108_light

Application purposes:

  • For preventing the spread of fire and combustion products through ceilings and walls

Characteristics:

  • Housing consists of two parts, detachable
  • High fire resistance - EI-180
  • Products are certified
  • Metal parts are painted with powder paint which increases the corrosion resistance
  • Easy assembly/disassembly
  • Coefficient of expansion is not less than 900%
  • Collar is triggered at 15 seconds at temperature of +150 °C, complete overlap occurs at the intersection at 4 minute
  • Keeps characteristics at temperatures from -50 °C to +80 °C
  • 30 years lifetime
  • Light type

Inner diameter: DN 110/108

Color: light gray

Download installation instruction: OGNEZA Fire collar OGNEZA Fire collar

OGNEZA Fire prevention symmetrical sleeve, d 110, d1 150 (price on request) [Code number: pm_110_150]
Details
pm_110_150

Application purpose:

  • For pipeline communications made of combustible plastic materials (PP, PE, PVC)
  • For residential (including multi-apartment) buildings, hotels and hostels, social and medical institutions, shopping centers, airports and railway stations, industrial enterprises, etc
  • To protect premises from fire and smoke

Characteristics:

  • It is an elongated fire sleeve equipped with two liners made of thermally expandable material (one on each side);
  • Provides double fire protection - just one sleeve is enough for the length of the entire ceiling;
  • The body is detachable, there is a tie-lock, so that the symmetrical fire coupling can be used on already installed pipelines;
  • Metal parts are powder coated for corrosion protection;
  • The clutch begins to work already at the 15th second when the temperature rises to +150 ° C, the complete overlap of the assembly occurs at the fourth minute;
  • Swelling ratio: not less than 900%;
  • Product color: grey;
  • Fire resistance limit: 180 minutes;
  • Service life: 30 years.

Operating principle:

During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.

Size Outside diameter Through Hole Diameter (minimum) Inner diameter Length Insert thickness
  mm mm mm mm mm
PM-110 125 128 110 300 7
OGNEZA Fire prevention symmetrical sleeve, d 110, d1 200 (price on request) [Code number: pm_110_200]
Details
pm_110_200

Application purpose:

  • For pipeline communications made of combustible plastic materials (PP, PE, PVC)
  • For residential (including multi-apartment) buildings, hotels and hostels, social and medical institutions, shopping centers, airports and railway stations, industrial enterprises, etc
  • To protect premises from fire and smoke

Characteristics:

  • It is an elongated fire sleeve equipped with two liners made of thermally expandable material (one on each side);
  • Provides double fire protection - just one sleeve is enough for the length of the entire ceiling;
  • The body is detachable, there is a tie-lock, so that the symmetrical fire coupling can be used on already installed pipelines;
  • Metal parts are powder coated for corrosion protection;
  • The clutch begins to work already at the 15th second when the temperature rises to +150 ° C, the complete overlap of the assembly occurs at the fourth minute;
  • Swelling ratio: not less than 900%;
  • Product color: grey;
  • Fire resistance limit: 180 minutes;
  • Service life: 30 years.

Operating principle:

During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.

Size Outside diameter Through Hole Diameter (minimum) Inner diameter Length Insert thickness
  mm mm mm mm mm
PM-110 125 128 110 200 7
OGNEZA Fire prevention symmetrical sleeve, d 110, d1 250 (price on request) [Code number: pm_110_250]
Details
pm_110_250

Application purpose:

  • For pipeline communications made of combustible plastic materials (PP, PE, PVC)
  • For residential (including multi-apartment) buildings, hotels and hostels, social and medical institutions, shopping centers, airports and railway stations, industrial enterprises, etc
  • To protect premises from fire and smoke

Characteristics:

  • It is an elongated fire sleeve equipped with two liners made of thermally expandable material (one on each side);
  • Provides double fire protection - just one sleeve is enough for the length of the entire ceiling;
  • The body is detachable, there is a tie-lock, so that the symmetrical fire coupling can be used on already installed pipelines;
  • Metal parts are powder coated for corrosion protection;
  • The clutch begins to work already at the 15th second when the temperature rises to +150 ° C, the complete overlap of the assembly occurs at the fourth minute;
  • Swelling ratio: not less than 900%;
  • Product color: grey;
  • Fire resistance limit: 180 minutes;
  • Service life: 30 years.

Operating principle:

During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.

Size Outside diameter Through Hole Diameter (minimum) Inner diameter Length Insert thickness
  mm mm mm mm mm
PM-110 125 128 110 250 7
OGNEZA Fire prevention symmetrical sleeve, d 110, d1 300 (price on request) [Code number: pm_110_300]
Details
pm_110_300

Application purpose:

  • For pipeline communications made of combustible plastic materials (PP, PE, PVC)
  • For residential (including multi-apartment) buildings, hotels and hostels, social and medical institutions, shopping centers, airports and railway stations, industrial enterprises, etc
  • To protect premises from fire and smoke

Characteristics:

  • It is an elongated fire sleeve equipped with two liners made of thermally expandable material (one on each side);
  • Provides double fire protection - just one sleeve is enough for the length of the entire ceiling;
  • The body is detachable, there is a tie-lock, so that the symmetrical fire coupling can be used on already installed pipelines;
  • Metal parts are powder coated for corrosion protection;
  • The clutch begins to work already at the 15th second when the temperature rises to +150 ° C, the complete overlap of the assembly occurs at the fourth minute;
  • Swelling ratio: not less than 900%;
  • Product color: grey;
  • Fire resistance limit: 180 minutes;
  • Service life: 30 years.

Operating principle:

During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.

Size Outside diameter Through Hole Diameter (minimum) Inner diameter Length Insert thickness
  mm mm mm mm mm
PM-110 125 128 110 300 7
OGNEZA Fire collar with elongated mounts, d 110 (price on request) [Code number: pm_110_dlinnie_ushi]
Details
pm_110_dlinnie_ushi

Application purposes:

  • For preventing the spread of fire and combustion products through ceilings and walls

Characteristics:

  • Housing consists of two parts, detachable
  • High fire resistance - EI-180
  • Products are certified
  • Metal parts are painted with powder paint which increases the corrosion resistance
  • Easy assembly/disassembly
  • Coefficient of expansion is not less than 900%
  • Collar is triggered at 15 seconds at temperature of +150 °C, complete overlap occurs at the intersection at 4 minute
  • Keeps characteristics at temperatures from -50 °C to +80 °C
  • 30 years lifetime
  • Length of mounting lugs is 70 mm
Outside diameter Inner diameter Height Thickness of thermally expanding liner Colour Weight
mm mm mm mm   gr
130,0 ± 3,0 110,0 ± 3,0 50,0/ 60,0 7,0 ± 1,0 light gray 300 ± 20/ 315± 20

Download installation instruction: OGNEZA Fire collar OGNEZA Fire collar

OGNEZA Fire collar, lock type "Light", gray, d 110 [Code number: pm_110_light]
Details
pm_110_light 420 rub

Application purposes:

  • For preventing the spread of fire and combustion products through ceilings and walls

Characteristics:

  • Housing consists of two parts, detachable
  • High fire resistance - EI-180
  • Products are certified
  • Metal parts are painted with powder paint which increases the corrosion resistance
  • Easy assembly/disassembly
  • Coefficient of expansion is not less than 900%
  • Collar is triggered at 15 seconds at temperature of +150 °C, complete overlap occurs at the intersection at 4 minute
  • Keeps characteristics at temperatures from -50 °C to +80 °C
  • 30 years lifetime
  • Lock type: Light

Installation method

PM structure

 

  • The case is a metal cuff and is made of cold-rolled or galvanized steel (thickness from 0.5 to 2 mm). Painted with weatherproof paint.
  • The case is connected using a reliable Russian-made latch made of galvanized steel.
  • The fire-retardant liner is located inside the coupling, held by the cloves bent inward. They also provide directional expansion of the fire retardant liner during a fire.
  • The eyelets with holes can be easily bent. Their length is 35 mm, which simplifies installation.

Color: gray

Size Inner diameter Height Outside diameter Insert thickness Weight
  mm mm mm mm kg
PM-110 110 50 130 7 0,300

Download installation instruction: OGNEZA Fire collar OGNEZA Fire collar

OGNEZA Fire collar, lock type "Light", red, d 110 [Code number: pm_110_light_krasnie]
Details
pm_110_light_krasnie 420 rub

Application purposes:

  • For preventing the spread of fire and combustion products through ceilings and walls

Characteristics:

  • Housing consists of two parts, detachable
  • High fire resistance - EI-180
  • Products are certified
  • Metal parts are painted with powder paint which increases the corrosion resistance
  • Easy assembly/disassembly
  • Coefficient of expansion is not less than 900%
  • Collar is triggered at 15 seconds at temperature of +150 °C, complete overlap occurs at the intersection at 4 minute
  • Keeps characteristics at temperatures from -50 °C to +80 °C
  • 30 years lifetime
  • Lock type: Light

Installation method

PM structure

 

  • The case is a metal cuff and is made of cold-rolled or galvanized steel (thickness from 0.5 to 2 mm). Painted with weatherproof paint.
  • The case is connected using a reliable Russian-made latch made of galvanized steel.
  • The fire-retardant liner is located inside the coupling, held by the cloves bent inward. They also provide directional expansion of the fire retardant liner during a fire.
  • The eyelets with holes can be easily bent. Their length is 35 mm, which simplifies installation.

Color: red

Size Inner diameter Height Outside diameter Insert thickness Weight
  mm mm mm mm kg
PM-110 110 50 130 7 0,300

Download installation instruction: OGNEZA Fire collar OGNEZA Fire collar

OGNEZA Fire collar, lock type "Light", gray, d 125 [Code number: pm_125]
Details
pm_125 1 048 rub

Application purposes:

  • For preventing the spread of fire and combustion products through ceilings and walls

Characteristics:

  • Housing consists of two parts, detachable
  • High fire resistance - EI-180
  • Products are certified
  • Metal parts are painted with powder paint which increases the corrosion resistance
  • Easy assembly/disassembly
  • Coefficient of expansion is not less than 900%
  • Collar is triggered at 15 seconds at temperature of +150 °C, complete overlap occurs at the intersection at 4 minute
  • Keeps characteristics at temperatures from -50 °C to +80 °C
  • 30 years lifetime
  • Lock type: Light

Installation method

PM structure

 

  • The case is a metal cuff and is made of cold-rolled or galvanized steel (thickness from 0.5 to 2 mm). Painted with weatherproof paint.
  • The case is connected using a reliable Russian-made latch made of galvanized steel.
  • The fire-retardant liner is located inside the coupling, held by the cloves bent inward. They also provide directional expansion of the fire retardant liner during a fire.
  • The eyelets with holes can be easily bent. Their length is 35 mm, which simplifies installation.
Outside diameter Inner diameter Height Thickness of thermally expanding liner Colour Weight
mm mm mm mm   gr
145 125 50 7 gray 355

Download installation instruction: OGNEZA Fire collar OGNEZA Fire collar

See also