Application purpose:
- For pipeline communications made of combustible plastic materials (PP, PE, PVC)
- For residential (including multi-apartment) buildings, hotels and hostels, social and medical institutions, shopping centers, airports and railway stations, industrial enterprises, etc
- To protect premises from fire and smoke
Characteristics:
- It is an elongated fire sleeve equipped with two liners made of thermally expandable material (one on each side);
- Provides double fire protection - just one sleeve is enough for the length of the entire ceiling;
- The body is detachable, there is a tie-lock, so that the symmetrical fire coupling can be used on already installed pipelines;
- Metal parts are powder coated for corrosion protection;
- The clutch begins to work already at the 15th second when the temperature rises to +150 ° C, the complete overlap of the assembly occurs at the fourth minute;
- Swelling ratio: not less than 900%;
- Product color: red;
- Fire resistance limit: 180 minutes;
- Service life: 30 years.
Operating principle:
During a fire, the thermally expanding liner of the fire muff expands tenfold, resulting in the formation of a solid foam-coke foam that fills the hole in the ceiling. This is quite effective at blocking fire.
Size |
Outside diameter |
Through Hole Diameter (minimum) |
Inner diameter |
Length |
Insert thickness |
|
mm |
mm |
mm |
mm |
mm |
PM-32 |
41 |
44 |
16, 20, 25, 32 |
200 |
4+(2+2+2+2) |